PowerPanel™ Business Edition
94
compare the key OCCUR to identify an event that has occurred or FINISH to identify an event that has
cleared.
11. What network protocol is used in PowerPanel
®
Business Edition?
SNMP is used on communications between Client, Center, PDU or UPS with remote management card.
HTTP and HTTPS are used between the Agent and the Client.
12. What the network ports are used by PowerPanel
®
Business Edition?
Port 3052 (UDP/TCP), port 53568 (TCP), port 162 (UDP) and port 53566(UDP)
13. I try to set the Client to establish to communication with one of PDUs. How do I identify the
targeted device IP?
Refer to the Easy-to-Setup Device IP
for details.
14. How do I ensure that the SNMP settings between the Client and UPS/PDU are properly setup?
To receive the trap notification from the UPS/PDU all the time, follow steps to verify the SNMP settings:
z Open the Network/Trap Notification page on the UPS/PDU web and the Security/Authentication
page on the Client.
z Confirm that the IP address of the Client can be found on the Network/Trap Notification page of the
UPS/PDU web. If the IP address can be searched, skip the step 3.
z If the IP address of the Client could not be found, click the Trap Receiver shortcut of the
Network/Trap Notification page to enter the Trap Configuration page. Enter the required data to
add a new trap receiver.
z If the IP address of the Client could be found, verify the SNMP settings are matched.
15. How do I determine that if my computer is using hibernation or not?
If the operating system is Windows 2000, Windows XP or Windows Server 2003, please follow the
below steps to enable the hibernation:
z Open Power Options in the Control Panel. (Go to Start > Control Panel > Power Options.)
z Click the Hibernate tab, and then select the Enable hibernate support option. Click the OK button to
close the Power Options dialog box. The hibernation has been enabled. If the tab is not available,
your computer doesn’t support this hibernation.
If the operating system is Windows Vista, Windows 7 or Windows Server 2008, please follow the
below steps to enable the hibernation.
z Open the Command Prompt dialog box.
z Use the command powercfg.exe -hibernate on to enable the hibernation.
16. Which series does my UPS model belong to?
Check the UPS model and determine to which series your UPS belongs: